Journal Search Engine
Search Advanced Search Adode Reader(link)
Download PDF Export Citaion korean bibliography PMC previewer
ISSN : 1225-0112(Print)
ISSN : 2288-4505(Online)
Applied Chemistry for Engineering Vol.14 No.5 pp.599-604
DOI :

Research Papers : Experimental Study on the Prediction of Ignition Risk by Cable Characteristics

Kang Jun Gu

Abstract

An experimental study on the spark test by RLC changes and the L/R test by cable allowable induction was carried out to predict the ignition risk by cable characteristics. Experimental data obtained from L/R test were compared with the those of Bass and IEC/EN. The standard spark test apparatus and three gas mixtures with each different concentration are used as the experimental apparatus and explosive gas mixtures. From the present results, it was observed that resistive, capacitive and inductive properties were shown different risk characteristics. The inductive voltage measured during circuitry on/off was much larger than resistive and capacitive cases. As a result of L/R ratio test, it was found that the allowable L/R ratio increased as the circuit resistance and the cable resistance increased and decreased as the voltage increased.

연구논문 : 케이블 특성에 의한 점화위험성 예측에 관한 실험적 연구

강준구,권영철

초록

케이블 특성에 의한 점화위험성을 예측하기 위하여 RLC 변화에 대한 불꽃점화 실험과 케이블 허용인덕턴스의 L/R 비율에 대한 실험을 수행하였다. 허용인덕턴스의 비율은 Bass와 IEC/EN의 계산과 서로 비교하였다. 불꽃점화시험을 위해 표준불꽃 점화시험 장치를 그리고 다른 농도를 가진 3종류의 혼합가스를 사용하였다. 실험결과로부터 저항성, 용량성, 유도성의 점화위험성은 서로 다르게 관찰되었다. 불꽃점화시험에 의한 전압과 전류파형은 저항성과 유도성의 경우에 구형파를 용량성의 경우에 톱니파의 형태를 가졌으며, 회로 개폐순간의 발생전압은 유도성이 저항성과 용량성보다 크게 나타났다. 한편, 허용 L/R 비율은 전원저항과 케이블저항이 높을수록 증가하며, 전압이 증가할수록 감소하였다.