Research Papers ; A Study on the Thermodynamic Simulation for an Absorption Heat Transformer and a Resorption Heat Pump

Byong Hun Min

Abstract

In general, water-lithium bromide solution is a well known working fluid used in an absorption heat pump. Because of problems of crystallization and corrosion in this solution, an absorption heat transformer, and a resorption heat pump for energy recovery have been investigated using methanol-glycerine solution as the working fluid. The simulated calculation of coefficient of performance (COP) was performed based on the thermodynamic properties of this working fluid over various operating conditions. COP of higher than 0.4 was obtained by raising industrial waste heat, 70 ~ 80 ℃, by 40 ℃ in both of systems. Comparison of COP for the two systems was difficult because the degree of freedom was different for each system. This study has shown that there was no COP difference between the absortion heat trasformer and the resorption heat pump under same pressure condition.

연구논문 : 변형 흡수 열펌프와 재 흡수 열펌프의 열역학적 모사 연구

민병훈

초록

일반적으로 H2O-LiBr 용액이 흡수 열펌프에서 주로 이용되어 왔다. 이 용액은 결정화와 부식의 단점 때문에 본 연구에서는 메탄올과 글리세린을 이용하여 에너지 회수를 위한 변형 흡수 열펌프와 재 흡수 열펌프 연구를 수행하였다. 이 물질의 상 평형 열역학 데이터를 이용하여 위 두 시스템의 성능계수(COP) 값을 각 기관의 조업 조건에 따라 모사 계산하였다. 70 ~ 80 ℃의 산업 폐열 온도를 가지고 40 ~ 50 ℃ 승온 시킬 때 성능계수 0.4 이상을 얻을 수 있었다. 변형 흡수 열펌프와 재 흡수 열펌프의 자유도 수 차이 때문에 성능계수 값을 정확히 비교하기는 어렵지만 동일한 압력 조건에서 위 두 시스템의 성능계수 값은 큰 차이가 없었다.