Applied Chemistry for Engineering Vol.11 No.1 pp.7-12
DOI :

Reaction Characteristics on the 2.25Cr-1Mo Specimen and Target tube by Micro-Water Leakage

Jeong Kyung Chai

Abstract

Small water leakage experiments were carried out using the 2.25Cr-1Mo steel specimen and target tube in liquid sodium atmosphere. The self-wastage phenomena, the plugging or reopening at leak path of the specimen was caused by sodium-water reaction products and corrosion precipitates from reaction of tube material and sodium. The reopening time of leak path in the plugged specimen was 180~290 and 30~40 minutes at the sodium temperatures at 400 and 450 ℃, respectively, and it had a tendency to decrease with the sodium temperature. Otherwise, penetration time into wall of the target tube was about 40 sec by reaction jet after the leak path reopened, and the mean leak rate was about 6 g-H2O/sec. The following correlation equation about the reopen time between sodium temperature and initial leak rate was obtained, τc=δ·g-0.83·10(3570/TNa-3.34),in 400~500℃ of liquid sodium atmosphere.

연구논문 / 미량 물 누출에 의한 2.25Cr-1Mo 시편 및 Target 에서의 반응특성

정경채,김병호

초록

액체 나트륨 분위기에서 2.25Cr-1Mo steel 시편을 통해 미량 물 누출 실험을 수행하였다. 미량의 물 누출로 인해 시편의 누출 경로가 막히거나 재개방되는 self-wastage 현상은 나트륨-물 반응에 의해 생성된 반응생성물과 나트륨과 튜브재질과의 부식 침전물이 주원인인 것으로 예상되었다. 본 실험에 사용되었던 시편으로부터 막혔던 누출 경로가 재개방되는데 걸리는 시간은 나트륨 온도가 400℃인 경우 180~290분, 450℃인 경우 30~40분을 나타내었으며, 온도가 증가할수록 재개방 시간은 감소되는 경향을 나타내었다. 또한 Target tube가 self-wastage에 의해 defect되는 시간은 누출경로가 재개방된 후 약 40초 경과된 다음 발생하였으며, 평균 물 누출율은 약 6 g-H2O/sec로 나타났다. 온도에 따라 재개방 시간을 나트륨 온도와 초기 누출량을 변수로 해서 correlation한 결과 400~500℃ 범위의 액체 나트륨 분위기에서 τc=δ·g-0.83·10(3570/TNa-3.34)와 같은 관계식을 얻을 수 있었다.

Figure

Table